Vatral® 150/650
Mortar and molded parts with thermal insulation properties
VATRAL® 150/650 panels: for lightweight constructions with precisely fitting molded parts such as walls, ceilings, cold storage and furniture construction.
VATRAL® 150/650 pipe shells: for thermal insulation at high temperatures, designed with or without diffusion-tight lamination.
By combining molded parts and mortar, even complicated constructions can be insulated without thermal bridges.
- Fire behavior: A1 according to DIN EN 13501-1:2019-05
- Application temperature: ≤ 900 °C
- Compressive strength: ≥ 0.3 MPa according to DIN EN 1015-11:2020-01
- Dry bulk density: approx. 125 kg/m³
- Chloride content: ≤ 0.01 % according to DIN EN 1015-17:2005-01
Application examples



- Thermal oil and high-temperature lines
- Shipbuilding . E.g. exhaust pipes
- power plants. E.g. on heat exchange pipes
Product information
areas of application
Vatral® 150/650 Technical Insulation Board is used in technical insulation. In combination with Vatral® 150/650 Technical
insulating mortar, even complicated constructions can be insulated without thermal bridges.
Vatral® 150/650 pipe shell is used in technical insulation. In combination with Vatral® 150/650 technical insulating mortar, even complicated constructions can be insulated without thermal bridges. With the use of Vatral® 200 fire protection adhesive Vatral® 150/650 pipe shells can be continuously laminated with a 0.05 mm or 0.1 mm coarse-grain aluminum foil.
processing
The mortar is ready to use. Before the
Mix slowly and thoroughly,
Do not dilute! Processing can be carried out with
steel filler. The substrate must
be dry and free of dust and grease. The
Room temperature during processing
must not be below 5 °C. The mortar can be applied after
it is completely dry, sanded, drilled and
be cut.
The panel can be sanded, drilled, cut and
and laminated. Suitable cutting devices
are among others: oscillating saw, electric saw or
Foxtail. Note dust formation. Under
Use of Vatral® 200 fire protection adhesive
can Vatral® 150/650 Technical Insulation Panels
continuous with a 0.05 mm or 0.1 mm
aluminum coarse-grain foil.
The pipe shell can be ground, drilled,
cut and laminated. Suitable
Cutting devices include: oscillating saw,
electric saw or foxtail. Note dust formation.
technical data
- Non-combustible (Euroclass A1 according to DIN EN 13501-1)
- Shipbuilding approval according to IMO FTPC Part 1
- High temperature resistance
- Hydrophobic finish (water rolls off.)
Modern silicone resins ensure reduced water absorption.
instructions
Wear suitable protective gloves and safety goggles. The information in the safety data sheet must be observed. Irritant effect in contact with eyes and skin. In case of contact with eyes or skin, rinse thoroughly with water.
Drying times
The finished modeled parts harden at room temperature, but can also be hardened in ovens (pre-drying 50-70 °C, final drying 100-150 °C, drying times depend on the thickness). Insulation with layer thicknesses > 3 cm should always be installed in combination with pre-dried boards, segments etc. to reduce the drying time. See Vatral® 150/650 technical insulation panel, Vatral® 150/650 pipe shell and Vatral® 150/650 segments.
Packaging and container sizes
Bucket: 2.5 – 10 – 25 liters